Toshiba Carrier BMS-SM1280HTLUL Service Manual page 47

Smart manager / central remote control
Hide thumbs Also See for Carrier BMS-SM1280HTLUL:
Table of Contents

Advertisement

No.
Check item
6
Power distribution
(*1)
check
7
Scheduled operation
(*1)
check
8
PC connection check
(*1)
on site
(*1) Target model of this description is Smart Manager (SM1280HTLUL) which can be connected to a PC through the Web.
No.
1
Operate the air conditioner for several hours with the controller in operation.
2
Perform manual meter-reading from the PC. "Option" > "Manual Meter-Reading" > "Go"
(Do not select "don't continue data reading".)
3
Wait for approx. 1 minute until a manual meter-reading file is created.
4
Selecting "Option" > "Manual Meter-Reading" displays the file created in "Data reading
completed".
5
Download a monthly report file with the Monthly Report Creation Software.
6
Select the file displayed in (4) in [File setting].
7
Check the output result of the monthly report created.
47
Procedure