Toshiba Carrier BMS-SM1280HTLUL Service Manual page 43

Smart manager / central remote control
Hide thumbs Also See for Carrier BMS-SM1280HTLUL:
Table of Contents

Advertisement

14-2.Procedure of Test Run Check
No.
Check item
1
PC connection check
(*1)
(*1) Target model of this description is Smart Manager (SM1280HTLUL) which can be connected to a PC through the Web.
No.
1
Start the browser software of the PC to be connected.
2
Enter http://the controller's IP address/index.html in the address bar of the browser, and
check that the logon window is displayed.
×
NG1:
Network Error
×
NG2:
The server is not found.
 OK:
The logon window is
displayed.
3
After entering TCC in User Name and TCC in Password, click "Logon" and make sure that
you can successfully logon.
×
NG1:
The dialog message,
"Logon failed." appears.
×
NG2:
The dialog message "No
response from the
server." or "The system
is being prepared."
appears.
×
NG3:
The dialog message
"The system is stopped."
appears.
 OK:
The list window displays
the indoor units set in the
setting file.
43
Procedure
Error message
1) Check if the browser proxy is correctly set.
1) Check if the network wiring is correctly installed. (Refer
to "15-1. Network Wiring")
2) Check if the PC's IP address is correct.
(Refer to "15-2. PC's IP Address")
3) Check if the controller's IP address is correct. (Refer to
"15-3. Controller's IP Address")
1) Proceed to the logon check.
Error message
1) The user name or password entered are incorrect.
Logon again with all the characters in upper case.
1) The controller is being initialized during the startup
process. Wait for 5 minutes and logon again.
1) Close the browser and turn off the controller. Wait for
30 seconds and turn on the controller. Wait for 5
minutes and logon again.
2) If the dialog message "The system is stopping."
appears again, initialize the setting file with the Setting
File Creation Software and turn off the controller.Wait
for 30 seconds and turn on the controller. Wait for 5
minutes and logon again.
3) When successfully logging on after the initialization,
upload again the setting file created, and check that
you can logon.
1) Proceed to the next check.