■ Checking Method (Flow Chart)
Checking start
After power supplied,
The location and
No
the pressure on LGMV
connection of connector
is normal before
is normal on PCB?
operating?
Yes
Voltage of 5V is output
from the PCB?
No malfunction of the pressure
Replace the pressure sensor
sensor
174
_TROUBLE SHOOTING GUIDE BOOK
No
Reconnection
Yes
No
PCB checking and replacement
Yes

11. Humidity Sensor

If the humidity sensor has problem such as sensor open or short, no error display is shown at outdoor
unit.
Normally LGMV shows humidity ratio such as below display box of LGMV.
However, if the humidity sensor open/short occurred, it displays as "0".
In case of the sensor fault occurred, the system is operated not as the dual sensing SLC (Temperature
+ Humidity) but as the SLC (Only Temperature)
This means that system is normally operated without humidity function even if humidity sensor has
problem.
LGMV
Humidity : "0"
175