Toshiba TCB-LD1UPE Installation & Operation Manual page 10

Leak detector

Advertisement

• Keep a space around the Leak Detector as detailed on the figure shown below.
50 mm
or more
• Install so the Leak Detector is within 300 mm of the floor. This is stipulated in regulations.
• Install this Leak Detector horizontally.
• Do not block the slit for gas detecting or place objects immediately in front of the gas
detector as this will mean leaks will not be detected.
• This Leak Detector should be mounted in a position where it can be easily accessed for
maintenance and repairs.
• Avoid the following locations for installation.
• By a window, etc. exposed to direct sunlight or external airflow
• In the shadow or backside of objects deviated from the room airflow
• Location where condensation occurs (The Leak Detector is not moisture proof or drip
proof)
• Location near heat source
• Uneven surface
• Location where there is a danger of mechanical damage being inflicted on the Leak
Detector
• Location where there is a danger of the generation of contaminants such as silicone gases
(siloxane, etc.), organic solvents/chloric gases, etc.
• Do not install the Leak Detector in a place where smoke, chemical agent, or organic solvent
is present.
Do not use gas equipment using combustion gas (LPG etc.) such as propane, butane, or
methane, an insecticide, or sprays or paints containing siloxane, near the Leak Detector.
The refrigerant leak detection sensor operates mistakenly, causing the air conditioner not to
operate.
Refer to the installation instructions supplied with the outdoor unit for details about the
location for installing the Leak Detector.