Instruction Codes; Reply Code - Toshiba CC-Link TOSVERT VF-S11 Option Instruction Manual

Hide thumbs Also See for CC-Link TOSVERT VF-S11:
Table of Contents

Advertisement

5.4. Instruction Codes

Code No.
Command mode selection read
1003H
Command mode selection write
2003H
Frequency setting mode
1004H
Frequency setting mode
2004H
Special monitor
0072H
read
Special monitor code read
0073H
write
Special monitor selection
00F3H
Trip history No.1, No.2 read
0074H
Trip history No.3, No.4 read
0075H
Frequency command value (RAM)
006DH
read
Option frequency command value
00EDH
(RAM) write *
Trip history clear
00F4H
Parameter all clear
00FCH
Inverter reset
00FDH
1000H to
1999H
Read parameters (RAM)
(1000H to
1F99H)
2000H to
Write parameters (EEPROM&RAM)
2999H
* The writing of frequency instructions serves as only writing to RAM area.
Note: The frequency value setting when power off and on or reset the inverter, the frequency setting is
reset (0Hz).

5.5. Reply Code

When executing the frequency setting (RYnD) or instruction code execution (RYnF), check
the reply code (RWr (n+2)) in the remote register after execution.
Reply code
Data
0000H
0001H
0002H
0003H
Contents
selection read
selection write
Item
Normal (No error)
Write error
Parameter selection error
Setting range error
0 : Terminal board
1 : Operation panel
0 :
Built-in potentiometer
1 :
VIA
2 : VIB
3 : Operation panel
4 : Serial communication
5 : UP/DOWN communication
6 : VIA + VIB (Override)
0000H to FFFFH
Monitor value selected after choosing
:
instruction code 00F3H.
Read the content which was monitored by special monitor.
Select the monitor code of special monitor.
Read the No.1(latest) to No.4(oldest) trip records.
Read the frequency command value (RAM).
Write the option frequency command value (RAM). *
9696H : Clear all trip history.
9696H : Clear all parameters. (Parameters other than
proofread values are made into factory default
settings.)
9696H : Reset the inverter. (This command is invalid when
the inverter is normal.)
To read parameters F000 to F912, add the triple figures that
follow Fxxx to 1000H. (Ex: F912 -> 912 + 1000 = 1912)
No error occurs when you select 1A00 to 1F99. Because
these parameters are for maintenance.
To write parameters F000 to F912, add the triple figures
that follow Fxxx to 2000H.
Normal completion of instruction code execution
Execution error.
(Write protected during operation)
Unregistered code number was set.
Set data is outside the setting data range.
- 19 -
E6581422③
Description
Detailed contents