Current Derating As A Function Of Pulse Frequency - Siemens SINAMICS S120 Equipment Manual

Chassis power units liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor Modules
5.6 Technical specifications
5.6.2.4

Current derating as a function of pulse frequency

When the pulse frequency is increased, the derating factor of the output current must be
taken into account.
This derating factor must be applied to the currents specified in the technical specifications
from Table 5-7 to Table 5-10.
Table 5-11
Order no.
6SL3325-...
1TE32-1AA0
1TE32-6AA0
1TE33-1AA0
1TE35-0AA0
Table 5-12
Order no.
6SL3325-...
1TE36-1AA0
1TE38-4AA0
1TE41-0AA0
1TE41-4AA0
1TG31-0AA0
1TG31-5AA0
1TG32-2AA0
1TG33-3AA0
1TG35-8AA0
1TG38-1AA0
1TG41-0AA0
1TG41-3AA0
Note
For pulse frequencies in the range between the specified fixed values, the relevant derating
factors can be determined by linear interpolation.
5-24
Derating factor of the output current as a function of the pulse frequency for devices with
a rated pulse frequency of 2 kHz
Power
Output current at pulse frequency
[kW]
Connection voltage 510 – 720 V DC
110
132
160
250
Derating factor of the output current as a function of the pulse frequency for devices with
a rated pulse frequency of 1.25 kHz
Power
Output current at pulse frequency
[kW]
Connection voltage 510 – 720 V DC
315
450
560
800
Connection voltage 675 – 1080 V DC
90
132
200
315
560
800
1000
1200
SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4
of 2 kHz [A]
210
260
310
490
of 1.25 kHz [A]
605
840
985
1405
100
150
215
330
575
810
1025
1270
Derating factor at pulse frequency
of 4 kHz
82 %
83 %
88 %
78 %
Derating factor at pulse frequency
of 2.5 kHz
72 %
79 %
87 %
95 %
88 %
84 %
87 %
82 %
85 %
95 %
86 %
79 %
Chassis Power Units Liquid Cooled