Table 5-9
Technical specifications for the Motor Module, 675 V – 1080 V DC (part 1)
Order number
Rated output current I
N
Base load current I
L
Base load current I
H
Max. output current I
max
Unit rating
1)
Power on basis of I
H
Rated DC link current
Connection voltages
- DC link voltage
- Electronics power supply
Output voltage
Rated pulse frequency
Max. pulse frequency without derating
Max. pulse frequency with derating
Electronics current drain (24 V DC)
Cooling type
DC link capacitance
Power loss
2)
- Air / Coolant
- Total losses
Max. coolant temperature:
- without derating
- with derating
Coolant requirement
3)
Liquid volume of integrated heat exchanger
Typ. pressure drop with volumetric flow
Sound pressure level
DC link/motor connection
Max. connection cross-section
DC link connection (DCP, DCN)
Motor connection (U2, V2, W2)
PE connection
Max. cable length
Degree of protection
Dimensions
Width
Height
Depth
Frame size
Weight
UL listed fuse
5)
Number (connected in parallel)
Rated current
Size acc. to DIN 43620-1
Rated output of a typical standard asynchronous motor at 690 V 3 AC.
1)
At rated pulse frequency
2)
This value applies to both coolant options, i.e. water and water / Antifrogen N mixture with 45 %
3)
Antifrogen N.
This value applies to the water coolant option; for other coolant types, see Chapter 8.
4)
In order to build a UL-approved system, it is absolutely essential to use the specified fuses.
5)
Chassis Power Units Liquid Cooled
SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4
6SL3325–
1TG31-0AA0
A
100
A
95
A
89
A
142
kW
90
kW
75
A
122
V
DC
V
DC
V
ACeff
kHz
1.25
kHz
1.25
kHz
5
A
1.0
Liquid cooling with integrated stainless steel heat exchanger
μF
2800
kW
0.075 / 1.075
kW
1.15
°C
45
°C
50
l/min
9
dm³
0.31
Pa
70000
4)
dB(A)
52
mm²
Busbar
mm²
2 x 95
mm²
2 x 95
m
IP00
mm
150
mm
728
mm
545
FXL
kg
41
3NE3 224
1
160
1
5.6 Technical specifications
1TG31–5AA0
1TG32–2AA0
150
215
142
208
134
192
213
312
132
200
110
160
183
263
675 to 1080
24 (20.4 – 28.8)
0 to 0.72 x DC link voltage
1.25
1.25
1.25
1.25
5
5
1.0
1.5
2800
4200
0.07 / 1.58
0.09 / 2.15
1.65
2.24
45
45
50
50
9
12
0.31
0.91
70000
70000
52
52
Flange connection with screws M12
Busbar
Busbar
2 x 95
2 x 240
2 x 95
2 x 240
300 (shielded) / 450 (unshielded)
IP00
IP00
150
150
728
1153
545
545
FXL
GXL
41
80
3NE3 225
3NE3 230-0B
1
1
200
315
1
1
Motor Modules
1TG33–3AA0
330
320
280
480
315
250
403
1.25
1.25
5
1.5
5800
0.116 / 3.264
3.38
45
50
12
0.91
70000
52
Busbar
2 x 240
2 x 240
IP00
150
1153
545
GXL
80
3NE3 233
1
450
1
5-19