System Description; Features Overview; Table 1-1: General Specifications - ABB RMC-100 User Manual

Remote modular controller
Hide thumbs Also See for RMC-100:
Table of Contents

Advertisement

1

System description

The Remote Modular Controller (RMC-100) provides measurement, automation, monitoring, alarming,
asset data management, control, and data logging applications. A single RMC-100 controller can
manage automation, liquids and gas measurement, and asset data concentration for very large
production and transmission facilities.
1.1

Features overview

The RMC provides backward-compatible functionality based on ABB Totalflow software,
communications, and I/O technologies. The existing process foundation and the new enhanced
technology manage liquid and gas measurement, automation, and asset data concentration for large-
scale production and transmission facilities. It is scalable down to a single-board RTU footprint for
smaller systems.
The RMC supports I/O and communication expansion.
The RMC supports dual, backward-compatible TFIO buses, doubling the I/O module capacity to 44
modules.
The table below provides the general specifications for the RMC.

Table 1-1: General specifications

Specification
Operating voltage
range
Nominal power
Weight
Dimensions
Input/Output
Maximum battery
capacity
Mounting
Operating
temperature
Electromagnetic
compatibility
EMC Directive
2004/108/EC
Hazardous location
certification
(North America)
1 0 | R MC-1 00 | 2 10 55 5 2MN A E
Description
12 – 24 Vdc (+/- 20% variation, acceptable input range 9 – 30 Vdc). All voltage
output connections of both the onboard and TFIO modules depend on the
operating power supply voltage connected to the CHARGER/EXT PWR port.
1.5 watts (5 A maximum with external options connection)
Minimum (no communication modules inserted): 1.708 lbs. (0.775 kg)
Maximum (both communication modules inserted): 1.816 lbs. (0.824 kg)
Width
Height
Depth
Installed Depth
6 DI/DO, 2 PI, 4 AI, and 1 AO
30 Ah
DIN rail mounts on a wall or enclosure that meets the environmental ratings for
the environment of the location
-40 °C to 60 °C (-40 °F to 140 °F) when used with battery
-40 °C to 70 °C (-40 °F to 158 °F) when no battery is used
Storage temperature of -40 °C to 85 °C (-40 °F to 185 °F)
Emissions (Other):
FCC CFR 47, Part 15, Subpart B, Class A (FCC Emissions)
IECS-03, Issue 4, CAN/CSA-CEI/IEC CISPR 11 Class A (Canada ITE Emissions)
AS/NZS CISPR 11, Class A (Australia/New Zealand)
Emission EN 61326-1: Radiated and conducted Class A
Immunity EN 61326-1 to:
EN 61000-4-2, ESD, 8 kV Air, 4 kV Contact
EN 61000-4-3, RFI, 10 V/m
EN 61000-4-4, EFT, 2 kV to DC, 1 kV to Signals
EN 61000-4-6, Conducted, 0.15-80 MHZ, 3 Vrms
According to standards for the assurance of fundamental safety requirements in
the United States of America:
UL No. 61010-1: "Safety Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use - Part 1: General Requirements"
ANSI/ISA 12.12.01: "Non-incendive Electrical Equipment for Use in Class I and
II, Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) Locations."
ANSI/UL 60079-0: "Explosive Atmospheres – Part 0: Equipment – General
Requirements"
ANSI/UL 60079-15: "Explosive atmospheres – Part 15: Equipment protection by
type of protection 'n' "
UL No. 50E: "Enclosures for Electrical Equipment, Environmental
7.56 inches (19.20 cm)
8.31 inches (21.11 cm)
1.72 inches (4.37 cm)
On DIN rail 1.79 inches (4.55 cm)

Advertisement

Table of Contents
loading

Table of Contents