SAVE P/C
ENTER FUNCTION NUMBER: &&
ABORT–F1 DOWN–F2 RD. TITLR–F3
Functions 60–67 –
Save P/C
Functions 90–99 –
Load P/C
SIMATIC VPU200/565 Programming Manual
SUPPORT FUNCTIONS
60. ALL
61. LADDER
62. VARIABLE
63. CONSTANT
64. LOOPS
65. SNSLOH SLSTMD
66. SF PROGRAMS
67. SF SUBROUTINES
Figure 7-7 Support Functions Menu, page 2
Functions 60–67, Figure 7-7, are used to save data from the P/C to a VPU
disk. The memory type saved is indicated by the name of the function; e.g.,
All, Ladder, etc.
Enter the number corresponding to the type of memory you wish to save;
press Return. A prompt asks whether you are sure you wish that function
performed. If you press F1(NO), the function is aborted. Pressing F2(YES)
begins the requested operation.
Note that for Function 60, "ALL" means that Ladder Memory, V-Memory,
K-Memory, Word I/O, Forced Word I/OF Discrete I/O, Forced Discrete I/O
Loops. Analog Alarms, SF Programs. SF Subroutines, I/O Configuration for
all bases and channels, Memory Configuration, and Scan Time will be saved
to disk.
Functions 90–99, Figure 7-7, are used to load data from the VPU disk to
the P/C. The memory type loaded is indicated by the name of the function:
e.g., All without IR, Ladder, Variable, etc.
Enter the number corresponding to the type of memory you wish to load to
the P/C; press Return. A prompt asks whether you are sure you wish that
function performed. If you press F1 (NO) the function is aborted. Pressing
F2 (YES) begins the requested operation.
Function 90, Load without IR, loads Ladder Memory, V-Memory, K-Memory,
Scan Time, Loops, Analog Alarms, SF Programs, SF Subroutines, I/O
Configuration for all bases and channels, and, Memory Configuration. It
does not load Word I/O, Forced Word I/O, Discrete I/O, nor Forced Discrete
I/O.
Function 98, Forced IR, loads Forced Word I/O (WX, WY) and Forced
Discrete I/O (X, Y, C).
LOAD P/C
90. ALL WITHOUT IR
91. LADDER
92. VARIABLE
93. CONSTANT
94. LOOPS
95. ANALOG ALARMS
96. SF PROGRAMS
97. SF SUBROUTINES
98. FORCED IR
99. WORD I/O
Using Support Functions