Test And Service Functions; Test Functions - Siemens SIMATIC S7-1500 System Manual

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Test and service functions

14.1

Test functions

Introduction
You have the option of testing the operation of your user program on the CPU. You monitor
the signal states and values of tags. You preassign values to tags to allow you to simulate
specific situations for program execution.
NOTE
Using test functions
Using test functions affects the program execution time and thus the cycle and response
times of the controller.
NOTE
Test functions in the RUN-Redundant system state: Check for sufficient free space
before a write function
Before a write function is performed, the system checks whether there is enough free space
on the SIMATIC memory cards of the CPUs for the function. Writing functions are online
functions with the PG/PC, for example, loading/deleting a block, test functions, loading a
modified user program in RUN-Redundant system state.
If there is not enough space on a SIMATIC memory card or on both SIMATIC memory cards,
the write function is aborted and the redundant system continues operation with the original
configuration. The redundant system will remain in the RUN-Redundant system state.
Requirements
• There is an online connection to the relevant primary or backup CPU. A simultaneous
online connection to both CPUs is not possible.
• An executable user program is available in the CPU.
• The redundant system must not be in the SYNCUP system state.
Exception: The test functions "Test with a force table" and "Trace function" are also
supported in the SYNCUP system state. However, there is no online connection during the
SYNCUP system state. You can find more information in this section.
344
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500rSimatic s7-1500h

Table of Contents