Installation
6.3 Installing the standard rail adapter
Figure 6-8  Mounting sequence of the DIN rail adapter to the DIN rail 35 mm x 7.5 mm or 35 mm x 15 mm
Mounting to the standard DIN rail 35 mm x 15 mm
To install DIN rail adapter on the standard DIN rail 35 mm x 15 mm, follow these steps:
1. Set the clamp onto the standard DIN rail.
2. The longer transverse edge of the adapter frame points toward the cabinet or box wall
(3).
3. Place the S7-1500R/H mounting rail on the adapter frame so that the groove in the
S7-1500R/H mounting rail fits into the groove in the adapter frame.
Place the S7-1500R/H mounting rail with the adapter frame onto the clamp (4).
4. Use screws to fasten the S7-1500R/H mounting rail to the standard rail adapter and the
standard mounting rail (tightening torque 5 Nm to 6 Nm).
164
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD