VersaMax PROFINET Scanner Specifications

PROFINET Support
RX3i CPU Version
Required
RX3i PNC Version
Required
Proficy Machine Edition
Version Required
Power Consumption
Module Dimensions
Carrier Required
Operating Temperature
Range
Number of Port
Connectors
USB Connector (for
firmware upgrades)
PNS Status and Control
Bits
I/O Data Update on the
PROFINET network
Number of IP addresses
Number of MAC
Addresses
I/O Station Maximum
Limits
RoHS Compliance
Configuration
For product standards, general operating specifications, and installation requirements, refer to
the VersaMax I/O Modules Manual, GFK-1504.
1-4
PROFINET Version 2.3 Class A IO-Device
Redundantly controlled operation conforms to PROFINET V2.3 Type S-2
System Redundancy.
Firmware version 8.00 or later
2.00 or later
Version 8.0 or later
IC200PNS001: 0.60A at 5VDC
IC200PNS002: 1.10A at 5VDC
Height: 132mm (5.2 inches), Width: 134mm (5.28 inches)
No. Carrier is integrated into the module.
0 to 60°C surrounding air temperature without a fan
IC200PNS001: Two RJ-45
IC200PNS002: Two SC-Duplex
One Micro-B connector. USB 2.0 compliant running at Full-speed
(12 MHz)
32 input status bits and 32 output control bits
Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms
and 512ms
One. Supports Classless Inter-Domain Routing (CIDR)
Three. One per external port and one internal. External MAC addresses
are only used for specialized Ethernet protocols such as MRP or LLDP
Number of I/O Modules per
station
I/O data per station
Yes
Configured using Proficy Machine Edition when used with a
PACSystems RX3i PROFINET Controller (PNC) module, as part
of an RX3i PROFINET network.
V2.3 GSDML file is available for import into 3
VersaMax PROFINET Scanner Manual – December 2013
8
2880 bytes total
1440 bytes of input data
1440 bytes of output data
rd
-Party tools.