Technical Data
4.8 Switch On To Fault Protection (50LC/SOTF)
4.8
Switch On To Fault Protection (50LC/SOTF)
Setting range
Operate level
Disengaging time
Operating time
Inhibited by
For more information about 50LC/SOTF, refer to
86
1 ⋅ I
to 20 ⋅ I
rated
rated
100 % I
, ± 5 %
s
< 50 ms
< 120 ms for 1.2 ⋅ I
rated
< 90 ms for 2 ⋅ I
rated
< 75 ms for 5 ⋅ I
rated
Binary input or inrush detector
3.8 Switch onto Fault Protection (50LC/SOTF)
C53000-G7040-C101-2, Edition 09.2020
.
Reyrolle, 7SR45, Device Manual