MULTI
Outdoor Unit
6. Capacity Correction Factor
■ Rate of change in capacity due to the branch piping length
Acoording to line up of each region, availability of indoor units may vary.
7k Btu/h (2.1 kW) or less models
Piping length(m)
7.5
10
15
20
25
9k Btu/h (2.5 kW) models
Piping length(m)
7.5
10
15
20
25
12k Btu/h (3.5 kW) models
Piping length(m)
7.5
10
15
20
25
18k Btu/h (5.0 kW) models
Piping length(m)
7.5
10
15
20
25
24k Btu/h (7.1 kW) models
Piping length(m)
7.5
10
15
20
25
130
Rate of change in capacity
Cooling(%)
100.0
98.4
95.8
93.2
90.6
Rate of change in capacity
Cooling(%)
100.0
98.0
94.8
91.6
88.4
Rate of change in capacity
Cooling(%)
100.0
97.6
93.8
89.9
86.1
Rate of change in capacity
Cooling(%)
100.0
98.6
96.4
94.1
91.9
Rate of change in capacity
Cooling(%)
100.0
98.2
95.4
92.4
89.6
Multiple piping type
Heating(%)
100.0
99.2
97.8
96.4
95.0
Heating(%)
100.0
99.0
97.4
95.8
94.2
Heating(%)
100.0
98.6
96.4
94.1
91.9
Heating(%)
100.0
99.6
99.0
98.3
97.7
Heating(%)
100.0
99.2
98.0
96.6
95.4