Line differential protection RED670
Version 2.2
Table 106. Negative sequence overcurrent protection LCNSPTOC
Function
Operate value, negative sequence
overcurrent
Reset ratio, negative sequence overcurrent
Operate time, start at 0 to 2 x I
Reset time, start at 2 x I
to 0
set
Operate time, start at 0 to 10 x I
Reset time, start at 10 x I
to 0
set
Critical impulse time, negative sequence
overcurrent
Impulse margin time, negative sequence
overcurrent
Independent time delay at 0 to 2 x I
Transient overreach, start function
Table 107. Zero sequence overcurrent protection LCZSPTOC
Function
Operate value, zero sequence overcurrent
Reset ratio, zero sequence overcurrent
Operate time, start at 0 to 2 x I
Reset time, start at 2 x I
to 0
set
Operate time, start at 0 to 10 x I
Reset time, start at 10 x I
to 0
set
Critical impulse time, zero sequence
overcurrent
Impulse margin time, zero sequence
overcurrent
Independent time delay at 0 to 2 x I
132
GUID-0E964441-43DE-43B6-B454-485FBBF66B5C v5
Range or value
(3 - 2500)% of IBase
>95% at (50–2500)% of IBase
Min. = 15 ms
set
Max. = 25 ms
Min. = 15 ms
Max. = 25 ms
Min. = 10 ms
set
Max. = 20 ms
Min. = 20 ms
Max. = 35 ms
10 ms typically at 0 to 2 x I
2 ms typically at 0 to 10 x I
15 ms typically
(0.000-60.000) s
set
<10% at τ = 100 ms
GUID-9F739808-04CA-4988-ABBC-1A444297FDB5 v5
Range or value
(3-2500)% of IBase
>95% at (50–2500)% of IBase
Min. = 15 ms
set
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 10 ms
set
Max. = 20 ms
Min. = 20 ms
Max. = 35 ms
10 ms typically at 0 to 2 x I
2 ms typically at 0 to 10 x I
15 ms typically
(0.000-60.000) s
set
© 2017 - 2022 Hitachi Energy. All rights reserved
Accuracy
±1.0% of Ir at I ≤ I
r
±1.0% of I at I > I
r
-
-
-
-
-
-
set
set
-
±0.2% or ±35 ms, whichever is greater
-
Accuracy
±1.0% of I
at I≤I
r
r
±1.0% of I at I>I
r
-
-
-
-
-
-
set
set
-
±0.2% or ±35 ms whichever is greater
1MRK 505 379-BEN R
Hitachi Energy