Mitsubishi Electric MELSERVO-J2 Series Instruction Manual page 116

Servo amplifier
Table of Contents

Advertisement

5. PARAMETERS
Class No. Symbol
16
*BPS
17
MOD
Downloaded from
ManualsNet.com
Name and Function
Communication baudrate
Used to select the RS-422/RS-232C communication baudrate and
choose various conditions for communication.
RS-422/RS-232C baudrate selection
0: 9600[bps]
1: 19200[bps]
2: 4800[bps]
Protocol checksum selection
0: Yes (checksum added)
1: No (checksum not added)
RS-422/RS-232C communication standard
selection
0: RS-422 used
1: RS-232C used
Communication response delay time
0: Invalid, reply sent in less than 400 s
1: Valid, reply sent in 400 s or more
Analog monitor output
Used to select the signals to be output to the analog monitor 1 (MO2)
and analog monitor 2 (MO2).
0
0
Setting
Analog Monitor 2 (MO2)
0
Servo motor speed ( 8V/max. speed)
1
Torque ( 8V/max. torque)
2
Servo motor speed ( 8V/max. speed)
3
Torque ( 8V/max. torque)
4
Current command ( 8V/max. current command)
5
Speed command ( 8/max. speed)
6
Droop pulses ( 10V/128 pulses)
7
Droop pulses ( 10V/2048 pulses)
8
Droop pulses ( 10V/8192 pulses)
9
Droop pulses ( 10V/32768 pulses)
A
Droop pulses ( 10V/131072 pulses)
search engine
Initial
Value
0000
0100
Analog Monitor 1 (MO1)
5 - 7
Setting
Unit
Reference
Range
Refer to
Section
Name
8.2.2
and
function
column.
Refer to
Section
Name
5.2.4
and
function
column.