Download Print this page
Siemens Climatix ECO POL224.00 Manual
Hide thumbs Also See for Climatix ECO POL224.00:

Advertisement

Quick Links

Climatix ECO
POL224.00, POL224.05
A6V11681604_enUS_b
2022-05-25
Free cooling with sensors, actuators, thermostats, fans and compressors
Free cooling based on single or dual dry bulb temperature, or combination
temperature + humidity sensors
Automatic switch-over for different control modes
Parameter settings based on climate zone, using GPS functionality in the Climatix
Mobile application
LED indication for free cooling operation, sensor operation and damper operation
Quick installation and easy commissioning with Climatix Mobile application
User Interface for normal operation, parameter setup and alarm notifications with
an LCD display and three operation buttons
RS485 port for BACnet MSTP slave or Modbus RTU slave communication
USB interface for firmware updates and WLAN connection
QR codes for quick access to download Climatix Mobile application and user
documentation
Smart Infrastructure

Advertisement

loading

Summary of Contents for Siemens Climatix ECO POL224.00

  • Page 1 Climatix ECO POL224.00, POL224.05 Free cooling with sensors, actuators, thermostats, fans and compressors ● Free cooling based on single or dual dry bulb temperature, or combination temperature + humidity sensors ● Automatic switch-over for different control modes ● Parameter settings based on climate zone, using GPS functionality in the Climatix Mobile application ●...
  • Page 2 Siemens QFM2160U or QFR9530 combination temperature/humidity sensor for enthalpy control ● Can be used with Siemens OpenAir® damper actuator GQD, GMA or GCA series ● 24Vac digital inputs for indication of occupancy, 3-stage Cooling Stage input, Shutdown, Heat Conventional, Heat Pump Changeover (HP(B)/HP(O)) or Preoccupancy ●...
  • Page 3 Yellow On Free cooling is running Green On Free cooling is available but not Green Blinking running Not economizing when it should Red Blinking Economizing when it should not Red On Sensors working ok Green On Siemens A6V11681604_enUS_b Smart Infrastructure 2022-05-25...
  • Page 4 Type Summary Type Order number Description POL224.00 S55392-C202-A100 POL224.00 Title24 Economizer Controller POL224.05 S55392-C203-A100 POL224.05 Title24 Econ Cont, no housing Order and Delivery When ordering, provide both name and type reference, e.g. Economizer Controller, POL224.00. Siemens A6V11681604_enUS_b Smart Infrastructure 2022-05-25...
  • Page 5 Programmable 24 Vac RDS120 A6V10807603 Thermostat Thermostat RDY2000 149-200 * The documents can be downloaded from Siemens US Download Center http://siemens.com/bt/download by specifying the datasheet number or part number as shown in the above table. Siemens A6V11681604_enUS_b Smart Infrastructure 2022-05-25...
  • Page 6 (For POL224.05) four spacers (M3.5 x L (L ≥10 mm) ) and four M3.5 screws are required. Metal spacers are recommended. ● (For POL224.00) two No. 6 3/4” self-tapping screws are required. ● Siemens does not provide screws or spacers with the product. They must be obtained separately. Siemens A6V11681604_enUS_b Smart Infrastructure...
  • Page 7 – Exhaust fan startup setpoint if exhaust fan is chosen – Etc. ● Change advanced settings like the following: – Damper position anti-freeze protection settings – Damper position during shutdown – Highest stage cooling delay time – Min. and max. leaving air temperature Siemens A6V11681604_enUS_b Smart Infrastructure 2022-05-25...
  • Page 8 Open Source Software (OSS) Software license overview These devices use Open Source Software (OSS). All Open Source Software components used in the product (to include copyrights and licensing agreement) are available at http://siemens.com/bt/download. Firmware version OSS document Device Document ID Title 0.1.23...
  • Page 9 1. This device may not cause harmful interference, and 2. this device must accept any interference received, including interference that may cause undesired operation FCC Caution: Changes or modifications not expressly approved by Siemens Switzerland Ltd. could void user authority to operate the equipment. United States representative https://new.siemens.com/us/en/products/buildingtechnologies/home.html...
  • Page 10 VFD Signal 0 to 10 Vdc Relay contact ratings 30 Vac (maximum power from class 2 input only), 3A run, and 7.5A inrush Detailed technical data are available in the documentation of the corresponding actuator. Siemens A6V11681604_enUS_b Smart Infrastructure 2022-05-25...
  • Page 11 Temperature -40° F to 158° F (-40 ° C to 70° C) (excluding HMI) Air humidity 5...95% r.h. (non-condensing) Mechanical ambient conditions Transport as per EN 60721-3-2 Class 2M2 Operation as per EN 60721-3-3 Class 3M2 Siemens A6V11681604_enUS_b Smart Infrastructure 2022-05-25...
  • Page 12 The product environmental declaration A5W00068298A contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). *) The documents can be downloaded from Siemens US Download Center. General data General See Dimensions [▶ Dimension Weight POL224.00...
  • Page 13 Relay 2, SPST relay, dry contact, digital input 2 for fan low speed with Y1 call Relay 3, SPST relay, dry contact, digital input 3 for fan low speed with G call Relay 4, DPST relay, dry contact, digital input 4 for fan high speed with Y2 call Siemens A6V11681604_enUS_b Smart Infrastructure...
  • Page 14 Fig. 2: Single Enthalpy Switchover + VFD + Thermostat + Exhaust Fan + Damper Actuator + OAT & MAT Sensors + OAH Sensor Siemens A6V11681604_enUS_b Smart Infrastructure 2022-05-25...
  • Page 15 Dimensions (in inch (mm)) POL224.00 POL224.05 Siemens A6V11681604_enUS_b Smart Infrastructure 2022-05-25...
  • Page 16 Issued by © Siemens Industry, Inc., 2022 Siemens Industry, Inc. Technical specifications and availability subject to change without notice. Smart Infrastructure 1000 Deerfield Pkwy Buffalo Grove IL 60089 +1 847-215-1000 Document ID A6V11681604_enUS_b Edition 2022-05-25...

This manual is also suitable for:

Climatix eco pol224.05