Fact_Set - Factory Setting; Ip-Typ - Type Of I/P Module; Ip_Comp - Ip Compensation - ABB TZIDC Manual

Digital positioner for the positioning of pneumatically controlled actuators
Table of Contents

Advertisement

38
TZIDC, TZIDC-200 DIGITAL POSITIONER | COI/TZIDC/TZIDC-200-EN REV. B
... 3 Configuration
... Parameter group 11: Safety position
FACT_SET – factory setting
You can use this parameter to reset the positioner to the factory
setting. This is necessary, e.g., if an already configured
positioner has to be installed on a different actuator and
subsequently reconfigured.
CAUTION
Risk of injury!
For safety reasons, after loading the factory settings you
must check whether the I/P module type that is set matches
the actual I/P module type present in the device.
Otherwise dangerous situations may occur when operating in
control mode. It may happen that the actuator is driven at full
speed to the end position.
Note
You can only load the factory settings when the actuator is in the
safe position (parameter FAIL_POS). Otherwise, the action is
inhibited and the message NO_F_POS is indicated in the display.
If you save the settings in the non-volatile memory after loading
the factory settings, operating mode 1.3 is automatically
activated on the operating level.
Load factory settings:
Press and hold the ENTER button, until the countdown displayed
on it has run from 3 to 0 and finished.
The positioner is reset to the factory settings. The message
COMPLETE is displayed.
Acknowledge the message by pressing the ENTER button.
Selection
FS_LOAD
Loads the factory settings
IP-TYP – Type of I/P module
Use this parameter to adapt the positioner software to the
installed I/P module. This is required when installing a different
I/P module type.
CAUTION
Risk of injury!
For safety reasons, after loading the factory settings you
must check whether the I/P module type that is set matches
the actual I/P module type present in the device. Otherwise
dangerous situations may occur when operating in control
mode. It may happen that the actuator is driven at full speed
to the end position.
CAUTION
For safety reasons, after restoring the positioner to the
factory settings you must check whether this parameter has
been correctly set.
IP_COMP – IP Compensation