Sw1_Actv - Active Direction Sw1; Sw2_Actv - Active Direction Sw2; Exit - Back To Work Level - ABB TZIDC Manual

Digital positioner for the positioning of pneumatically controlled actuators
Table of Contents

Advertisement

TZIDC, TZIDC-200 DIGITAL POSITIONER | COI/TZIDC/TZIDC-200-EN REV. B
SW1_ACTV – Active Direction SW1
With this parameter you define whether a message is to be
triggered for exceeding or falling below switching point SW1.
EXCEED
Message when exceeding switching point SW1.
FALL_BEL
Message when falling below switching point SW1.
SW2_ACTV – Active Direction SW2
With this parameter you define whether a message is to be
triggered for exceeding or falling below switching point SW2.
EXCEED
Message when exceeding switching point SW2.
FALL_BEL
Message when falling below switching point SW2.
EXIT – Back to work level
With this parameter you can leave the configuration level. The
positioner returns to the operating level. Here you can either
save data in the non-volatile memory or discard all previously
made changes (also the changes in other parameter groups).
To exit the configuration level (with or without saving), press
and hold the ENTER button, until the countdown has run from 3
to 0 and finished.
The active saving process is indicated by the message NV_SAVE.
After saving a plausibility check is executed.
If an error occurs during the check or while saving, the data
cannot be saved and an error message is displayed instead (see
Chapter Error codes on page 40).
Selection
NV_SAVE
Saves settings in the non-volatile memory.
CANCEL
Discards all changes made since the last permanent
save operation.
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tzidc-200

Table of Contents