Separating Power Wiring and Communication Cables
Avoid running the power wiring and communication cable alongside each other; there is a strong likelihood of operation malfunction
due to electrostatic and electromagnetic interference.
• If running the power wiring and communication cable alongside each other cannot be avoided, see the table below for minimum required
distances.
Table 13: Power Wire and Communications Cable Minimum Required Separation Allowable Distances.
Capacity of Power Supply Wiring (current)
100V or more
The figures above are based on parallel lengths up to 328 feet long. For lengths in excess of 328 feet, the distances will have to be recalculated in
1
direct proportion to the additional line lengths involved.
If the power supply waveform continues to exhibit some distortion, the space between the power wiring and communication cable must be in-
2
creased.
Do not secure the power wiring and communication cables together. It will result in equipment malfunction.
Do not run the power wiring and the communication cable in the same conduit. It will result in equipment malfunction.
Do not run both in the same conduit.
Exceeding 100A
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
10A
50A
100A
ELECTRICAL
General Information
Required Minimum Distance
1,2
12 inches
20 inches
40 inches
60 inches