Step 3 On the home screen of the display module, choose Settings > System Settings >
Common Settings, and set Motorized Damper to Enable.
----End
3.6.8 (Optional) Installing T/H Sensors Outside a Cabinet and
Cables
Context
T/H sensors outside the cabinet are installed to detect the temperatures of
cold/hot aisles. They can be flexibly installed on the server cabinet based on onsite
situation. It is recommended that the T/H sensors be deployed near heat sources
in the hot aisle, or near places that lack cooling capacity in the cold aisle. Place
the T/H sensors outside the cabinet adjacent to the smart cooling product without
directly facing the exhaust vents of the smart cooling product.
Procedure
Step 1 Connect the T/H sensors outside the cabinet and the T/H sensors at the air return
side in series.
Figure 3-52 Connecting T/H sensors (upflow model)
(1) T/H sensor outside the cabinet
Issue 07 (2021-12-30)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
3 Installation
76