Configuration And Settings; Scaling Analog Values Into Physical Values In The Logo - Siemens LOGO! 0BA7 Manual

Pi controller for simple applications - optimum motor speed control
Table of Contents

Advertisement

5 Configuration and Settings

Configuration and Settings
5
5.1
Scaling analog values into physical values in the
LOGO!
Table 5-1
No.
1.
Coming and going analog values can be
optionally scaled by means of the analog
blocks so that the user can have real physical
values (such as pressure, temperature,
revs/min) displayed in the LOGO!.
2.
Set the measuring range of the incoming
signal of the sensor to the real physical values.
No decimals can be entered in the physical
values.
For example: analog input signal 0 - 10V
corresponds to a physical pressure of 0 - 2.50
bar.
In the properties of the PI controller block, set
the following:
Minimum (1): 0
Maximum (2): 250
Integration time (3): 2s
The parameter "Gain" (4) is calculated
automatically.
Set23_RegSim
Entry ID: 23753479,
V2.3.S,
Function
02/2014
Comments
20