Emc Compliant Installation Guidelines - Toshiba Q9 Plus Bypass ASD Installation & Operation Manual

Hide thumbs Also See for Q9 Plus Bypass ASD:
Table of Contents

Advertisement

EMC Compliant Installation Guidelines

The Q9 Plus Bypass ASD/Q9 Plus Bypass Box shall be installed in accordance with the following
guidelines.
1.
Filtering — An input filter shall be used with the ASD. A Schaffner FN258 series input filter of the
appropriate rating shall be used and mounted adjacent to the ASD.
2.
Mechanical — The ASD and the associated equipment shall be mounted on a flat metallic
backplane. A minimum space of 5 cm (2 inches) shall exist between the ASD and the filter to allow
for ventilation. The filter output cable is to be connected from the bottom of the filter to the ASD
power input and is to be the minimum length required for a connection.
Units received as an Open Chassis shall not be placed into operation until being placed into an
approved enclosure that will protect personnel against electrical shock.
Opening and closing of enclosures or barriers shall be possible only with the use of a key or a tool.
3.
Cabling — The cables of the input power, filter, and motor shall be of the appropriate current
rating. The cables shall be connected in accordance with the guidelines of the manufacturer and the
applicable local and national agencies. A 4-core screened cable (such as RS 379-384) is to be used
for the power and earth connections to minimize RF emissions. Control cabling must be screened
using P/N RS 367-347 or a similar component.
4.
Grounding — The mains (input) ground shall be connected at the ground terminal provided on the
filter. The filter and motor shall be grounded at the ground terminals provided in the ASD.
5.
Screening — The mains (input) screen is to be connected to the metallic back-plane at the filter;
remove any finish coating as required. The screen over the filter output cables, the motor cable
screen, and the control wire screens must be connected to the ASD case using glands or conduit
connectors. The motor cable screen shall be connected to the motor case. When using a braking
resistor, the cabling between the resistor and ASD shall also be screened. This screen shall connect
to both the ASD enclosure and the resistor enclosure.
See the Q9 Plus Bypass ASD/Q9 Plus Bypass Box Filter Selection below for the recommended input
filters for a given typeform.
Q9 Plus Bypass ASD/Q9 Plus Bypass Box Filter Selection Table
230V
VT130
Q9+2015I
Q9+2025I
Q9+2035I
Q9+2055I
Q9+2080I
Q9+2110I
Q9+2160I
Q9+2220I
Q9+2270I
Q9+2330I
Q9+2400I
BYP2-100E
BYP2-125E
12
Filter
460V
Number
FN258-7
Q9+4015I
Q9+4025I
FN258-16
Q9+4035I
Q9+4055I
FN258-30
Q9+4080I
FN258-42
Q9+4110I
FN258-75
Q9+4160I
Q9+4220I
FN258-100
Q9+4270I
FN258-130
Q9+4330I
FN258-180
Q9+4400I
FN258-130
FN258-180
Filter
Number
Q9+4500
FN258-7
Q9+4600
Q9+4750
Q9+410K
FN258-16
Q9+412K
BYP4-070E
FN258-30
BYP4-080E
FN258-42
BYP4-100E
BYP4-125E
FN258-55
BYP4-160E
FN258-75
Q9 Plus Bypass ASD/Bypass Box Installation and Operation Manual
Filter
460V
Number
FN258-100
FS5236-130
FS5236-180
FS5236-300
FN258-100
FN258-130
FN258-180
FS5236-300