INSTALLATION

OEM ENCLOSURE DESIGN
These power cells should be totally enclosed in
sheet metal structures that comply with the
applicable requirements of NEMA Standards
Publications ICS 6 and 250 for enclosures for
industrial systems. The minimum controller
compartment size is 30 inches wide by 30 inches
high by 36 inches deep.
The power cell must be securely attached to the
floor of the controller compartment. Four holes
are provided in the cell base for anchoring using
5/16-18 bolts or studs. In addition, four threaded
inserts are provided which will accept 5/16-18
bolts installed from the underside of the cell, for
use if the compartment floor is located above
floor level. Refer to Fig. 17 for location of
mounting points.
The right front corner of the OEM structure
should include a flange of approximately 4
inches in width with a cutout for the operating
handle to extend through. The dimensions and
location of the handle cutout are given in Fig. 20.
The cell should be positioned in the enclosure as
far to the right and as far to the front as possible.
The compartment door should have flanged
edges, which result in a dimension of 1.25
inches from the inside of the door to the front of
the cell as shown in Fig. 20.
The door interlock that is provided with the kit
should be attached to the inside of enclosure
door at the specified location (Fig. 20).
Fig. 17 Power Cell Mounting
Page 15