ABB Relion 670 Series Applications Manual page 336

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 14
Control
789OPTR (bay 1)
789OPTR (bay 2)
789OPTR (bay n-1)
VP789TR (bay 1)
VP789TR (bay 2)
VP789TR (bay n-1)
EXDU_BPB (bay 1)
EXDU_BPB (bay 2)
EXDU_BPB (bay n-1)
ANSI04000477 V1 EN-US
Figure 136: Signals from bypass busbar in line bay n
14.4.2.3
Signals from bus-coupler
If the busbar is divided by bus-section disconnectors into bus sections, the busbar-busbar
connection could exist via the bus-section disconnector and bus-coupler within the other bus
section.
(WA1)A1
(WA2)B1
(WA7)C
ANSI04000479 V1 EN-US
Figure 137: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BC_12_CL
BC_17_OP
BC_17_CL
BC_27_OP
BC_27_CL
VP_BC_12
Table continues on next page
330
. . .
. . .
. . .
. . .
. . .
. . .
Section 1
ABC_LINE
ABC_BC
A bus-coupler connection exists between busbar WA1 and WA2.
No bus-coupler connection between busbar WA1 and WA7.
A bus-coupler connection exists between busbar WA1and WA7.
No bus-coupler connection between busbar WA2 and WA7.
A bus-coupler connection exists between busbar WA2 and WA7.
The switch status of BC_12 is valid.
© Copyright 2017 ABB. All rights reserved
BB7_D_OP
AND
VP_BB7_D
AND
EXDU_BPB
AND
en04000477_ansi.vsd
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_LINE
1MRK 511 401-UUS F
A2
B2
C
ABC_BC
en04000479_ansi.vsd
Bay control REC670
Application manual