Name
DC input module
AC input module
DC output module
AC output module
Relay output
module
Analog input
module
Analog output
module
Status change
detector module
Pulse input module PI312
SUPPLEMENTARY
• The basic unit requires a basic unit expansion interface module; an expansion unit requires an
expansion interface module.
• There is no limit on combination of base types (five types for basic unit, and two types for expan-
sion unit).
• When using expansion units, install an expansion interface module on each expansion base. The
expansion cable length between expansion units is 4 m max., with total length being 8 m max.
• Whether or not a power supply module is required for an expansion interface module is determined
depending on the current consumption of 5 V in the I/O module used in the expansion unit.
• Depending on whether or not a power supply module is installed for an expansion unit, it may be
necessary to switch the power supply module plug on the expansion interface module.
• Be sure to install a power supply module (PS361/332) on each expansion unit (0-1, 1-1, 2-1, 3-1).
• A G3 I/O module cannot be installed on the basic unit in duplex configuration.
NOTE
• For the types of I/O modules for the direct I/O system (G3 I/O system), refer to the "model 3000
Direct I/O Module User's Manual" (6F8C0867).
6F8C0882
Table 1-4 I/O Modules
Type
DI334
32 points (8 points/common), 12 to 24 Vdc, 10 mA/point
DI334H
32 points (8 points/common), 12 to 24 Vdc, 10 mA/point, High-speed
response
DI344
32 points (8 points/common), 48 Vdc, 5 mA/point
DI335
64 points (8 points/common), 24 Vdc, 5 mA/point
DI335H
64 points (8 points/common), 48 Vdc, 5 mA/point, High-speed
response
DI333D.
16 points (1 point/common), 12 to 24 Vdc, 11.4 mA/point
DI353D
16 points (1 point/common), 110 Vdc, 2.6 mA/point
16 points (1 point/common), 100 Vdc, 18 mA/point
DI334S
Data
32 points 12 to 24 Vdc, 8 mA/point
Strobe
2 points, 24 Vdc, 10 mA/point
IN354
32 points (8 points/common), 100 to 120 Vac, 10 mA/point
IN364
32 points (8 points/common), 200 to 240 Vac, 10 mA/point
DO333
16 points (8 points/common), 12 to 24 Vdc, 2 A/point, 5 A/common
DO334
32 points (16 points/common), 12 to 24 Vdc, 0.5 A/point, 5 A/common
DO344
32 points (16 points/common), 48 Vdc, 0.5 A/point, 5 A/common
DO335
64 points (8 points/common), 5 to 24 Vdc, 100 mA/point
DO334S
32 points (16 points/common), 12 to 24 Vdc, 0.5 A/point, with strobe
AC363
16 points (8 points/common), 100 to 240 Vac, 2 A/point, 5 A/common
AC364
32 points (16 points/common), 100 to 240 Vac, 0.5 A/point, 3.2 A/
common, 5 A/module
RO364
32 points (8 points/common), 240 Vac/24 Vdc, 2 A/point, 5 A/common
RO363S
16 points (Independent relays), 240 Vac/24 Vdc, 2 A/point
8 ch (Non insulated between channels), ±5 V/ ±10 V/0 to
AD368
Voltage
input
5 V/0 to 10 V
Current
8 ch (Non insulated between channels), 4 to 20 mA/0 to
input
20 mA
AD318
8 ch (Transformer-insulated between channels), Voltage input
(0 to 5 V)
AD328
8 ch (Transformer-insulated between channels), Current input
(0 to 20 mA)
AD338
8 ch (Transformer-insulated between channels), Voltage input (±10 V)
4 ch, Voltage output (± 5 V/ ± 10 V/0 to 5 V/0 to 10 V)
DA364
DA374
4 ch, Current output (4 to 20 mA/0 to 20 mA)
CD332
8 points (8 points/common), 12 to 24 Vdc
2 ch, 50 kpps, 5/12 Vdc
1.4 Connection with G3 I/O System
Specification
1
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

3000