. Multiple outdoor units control
Wiring specification and field supply parts
Model and specifications
Item
Name
External
Outputs
Use sheathed vinyl coated cord or cable.
output
wire
Max. 30 m
function
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.5 mm² to 1.25 mm²
Solid wire: ø0.65 mm to ø1.2 mm
Note: Do not connect multiple water circulation pumps directly to each output (OUT1). In such a case, connect them via (a) relay(s).
PAC-SIF051B-E
CN108
FTC4 (Slave)
LED4
SW2
SW4
1
1
6
8
SW1
1
LED3
8
CNW12
CN21
(RED)
(YLW)
TBIN
2
4
1
2
3
4
1
3
1
4
1
3
TBOUT
<Fig. ..3>
Signal inputs
Name Terminal block Connector
RC
TBIN 1-2
IN2
TBIN 3-4
CN2F
Wiring specification and field supply parts
Model and specifications
Item
Name
Signal input
Signal input wire
Use sheathed vinyl coated cord or cable.
function
Max. 10 m
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.5 mm² to 1.25 mm²
Switch
Non-voltage "a" contact signals
Remote switch: minimum applicable load 12V DC, 1mA
Thermistor inputs
Name
Terminal block Connector
TH2
CN21
THW1
CNW12 1-2 Thermistor (Flow water temp.)
THW2
CNW12 3-4 Thermistor (Return water temp.)
Note:
Do not splice the wiring to extend or shorten it, or this could affect correct monitoring of each temperature.
If the wiring is too long, bundle it with a strap to adjust the length.
Output
Name
Terminal block Connector Item
OUT1
TBOUT 1-2
N L
1 2
3 4
TBOUT
OUT1
<Fig. ..4>
Wiring specification and field supply parts
Model and specifications
Item
Name
External
Outputs
Use sheathed vinyl coated cord or cable.
output
wire
Max. 30 m
function
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.5 mm² to 1.25 mm²
Solid wire: ø0.65 mm to ø1.2 mm
Note: Do not connect multiple water circulation pumps directly to each output (OUT1). In such a case, connect them via (a) relay(s).

LED1
CNS2
(RED)
S1
S2
S3
3 1
L
N
TB6
Item
Communication cable between indoor units
Flow switch input
Solid wire: ø0.65 mm to ø1.2 mm
Item
Thermistor (Ref. liquid temp.)
Water circulation pump 1 output
OFF (Open)
OFF (Short)
Refer to SW2-2 in <9.6 Dip Switch Functions>.
Optional part model
Signal/Max current
OFF
ON
OFF
ON
230V AC 1.0 A Max