4. Electrical work
4.5.3 Outputs
Name
Terminal block Connector Item
OUT1
TBO.1 3-4
OUT2
TBO.1 5-6
OUT3
TBO.1 7-8
OUT4
TBO.1 9-11
TBO.1 12-13
OUT5
TBO.1 13-14
OUT6
TBO.3 1-2
OUT7
TBO.3 3-4
OUT8
TBO.2 11-12 —
OUT9
TBO.2 9-10
CNIH
OUT11 TBO.2 1-2
OUT12 TBO.2 3-4
OUT13 TBO.2 7-8
BC
TBO.3 5-6
OUT10 TBO.1 1-2
BHT
TBO.2 13-14 CNBHT
N L N L N L N
1 2
3 4 5
6 7 8
9 10 11
TBO.1
OUT10
OUT1 OUT2 OUT3
OUT4
Wiring specification and field supply parts
Model and specifications
Item
Name
External
Outputs
Use sheathed vinyl coated cord or cable.
output
wire
Max. 30 m
function
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.5 mm² to 1.25 mm²
Solid wire: ø0.65 mm to ø1.2 mm
Note:
1. When the hydrobox is powered via outdoor unit, the maximum grand total current of (a)+(b) is 3.0 A.
2. Do not connect multiple water circulation pumps directly to each output (OUT1, OUT2, and OUT3). In such a case, connect them via (a) relay(s).
3. Connect an appropriate surge absorber to OUT10 (TBO.1 1-2) depending on the load at site.
Water circulation pump 1 output (Space heating & DHW)
Water circulation pump 2 output (Space heating for Zone1) OFF
Water circulation pump 3 output (Space heating for Zone2) OFF
3-way valve (2-way valve 1) output
Mixing valve output
Booster heater 1 output
Booster heater 2 output
Booster heater 2+ output
Immersion heater output
Error output
Defrost output
2-way valve 2 output
Booster heater protection output
Boiler output
Thermostat for booster heater
L
N
L
N L
12 13 14
1 2
TBO.2
Close Open
OUT11
OUT5
OFF
ON
OFF
ON
ON
ON
Heating
DHW
Stop
Close
Stop
Open
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Normal
Error
Normal
Defrost
DHW
Heating
OFF
ON
(BHT open)
(BHT short)
OFF
ON
Thermostat Normal: short / High temp.: open
N L
N L
N L
N L
N
3 4 5
6 7 8
9 10 11
12 13 14
OUT12
OUT13
OUT9
OUT8
BHT
Signal/Max current
Max. total current
230V AC 1.0 A Max
3.0 A (a)
230V AC 1.0 A Max
230V AC 1.0 A Max
230V AC 0.1 A Max
230V AC 0.1 A Max
230V AC 0.5 A Max (Relay)
230V AC 0.5 A Max (Relay)
230V AC 0.5 A Max (Relay)
3.0 A (b)
230V AC 0.5 A Max (Relay)
230V AC 0.5 A Max
230V AC 0.5 A Max
230V AC 0.1 A Max
230V AC 0.5 A Max
non-voltage contact
• 220 - 240V AC (30V DC)
0.5A or less
• 10 mA 5V DC or more
L
L
L
1 2
3 4 5
6
TBO.3
OUT6
OUT7 BC
21