Case as V Standard 2 sets.
IP address : 172.16.64.xx (xx indicates the value of the station address
setting switches)
Subnet mask : 255.255.192.0
Case as the Any sets.
In this case, the values set by the tool have precedence in operation over
the value of the station address setting switch.
• Total number of multicast: Set a value in the range of 0 to 4. "0"
• Multicast IP1-IP4:
• Scan enabled:
• High speed scan cycle time:
• Middle speed scan cycle time: Set a value in the range of 2 to 1000 (the
• Low speed scan cycle time:
• Scan stop at all hosts down: The default setting is "No." By default,
when a controller is down, the down controller stops the transmission of
only the scan block with the transmission right. The remaining scan
blocks are continued. If "Yes" is selected, when all the controllers are
down, the transmission of the scan blocks of all the controllers with the
transmission right is stopped.
• Receiver:
• Max length between nodes:
• Max repeater connections:
Unified Controller nv-pack series TC-net 100(JTNI)Extended card Instruction Manual
3.3 Setting with the Engineering Tool
indicates none is used.
Set an address from the 15 addresses from
225.224.0.1 to 225.224.0.15.
To register multi-cast addresses, align them to
the top.
Select "Yes" online and write to the JTNI to
start or stop scanning from the engineering
tool.
After selecting "Yes," the parameter returns to
"No" when the JTNI restarts.
Set a value in the range of 10 to 1600 (the
unit is 0.1ms). "50" indicates 5ms.
unit is 1ms). "50" indicates 50ms.
Set a value in the range of 2 to 10000 (the
unit is 1ms). "500" indicates 500ms.
Select from Auto select/A select/B select.
Set an integer value for the distance
between the farthest nodes. The default
value is 8km. Using the default value is
recommended. The value can be changed if
system adjustment is required. For example,
if the distance is 7.3km, set "8km."
Set a value for the path with the most
repeater stages. The default value is 3.