Chapter 3 Setting
3.2
Network Parameter Setting
The network parameters can be set with the operation mode setting switches
and station address setting switches.
For the JTNI, the following network parameters must be set.
• IP address type
• Station address
Three IP address types are provided; nv series 1, nv series 2, Any, as tool. Also,
it can be select with the engineering tool.
3.2.1 Network ID and subnet mask
nv series 1 setting (Standard setting)
Use the standard setting switches to set the IP address type to [V standard 1].
This is the standard setting of the unified controller system.
Network ID: 172.16.64.XX
(XX indicates the value of the station address setting switches)
Subnet mask : 255.255.192.0
nv series 2 setting
Use the engineering tool and setting to set the IP address type to [V standard
2].
This setting is used for expansion of the TC-net 100, and not used normally.
Network ID: 172.31.64.XX
(XX indicates the value of the station address setting switches)
Subnet mask : 255.255.192.0
Arbitrary setting
Use the engineering tool and setting to set the IP address type to [Any].
When this setting is selected, it can be set freely from the engineering tool,
and the value has precedence over the value of the station address setting
switches.
However, the following cannot be used in the IP address.
• Addresses starting with 127(7Fh)
• Addresses with all bits of the network address are "0" or "1"
14