Samsung BACnet MIM-B17N User Manual page 54

Data management server2 for air conditioner
Hide thumbs Also See for BACnet MIM-B17N:
Table of Contents

Advertisement

Indoor Unit Usage Restriction_Temperature Limit in Cool/Heat mode
You can set temperature lower/upper temperature limit in
cool/heat mode.
1
Click [Control and Monitoring]
restriction] when DMS2 web page menu screen appears.
2
Press [Edit] button.
3
Set the lower/upper temperature limit.
You can set lower/upper temperature limit by selecting
'Enable'/'Disable'.
Lower temperature limit range: 18℃(64°F)~30℃(86°F)
Upper temperature limit range: 16℃(61°F)~30℃(86°F)
ERV PLUS and Fresh duct cannot set the lower temperature
limit in Cool mode or upper temperature limit in Heat mode.
4
Click [Save].
Indoor unit usage restriction setting will be saved.
[Indoor unit usage
53
E-