Samsung BACnet MIM-B17N User Manual page 31

Data management server2 for air conditioner
Hide thumbs Also See for BACnet MIM-B17N:
Table of Contents

Advertisement

Control and Monitoring (Continued)
Controlling a Fresh duct
30
E-
1
Click [Control and Monitoring] when DMS2 web page menu
screen appear.
[Control and Monitoring] screen will appear when you
log-in to DMS web page.
2
Check the current status of a Fresh duct.
Check the status of a Fresh duct through the status display
window.
When the selected Fresh duct is switched on, the remote
controller panel will be automatically activated.
3
Turn the Fresh duct on by clicking [
Remote controller panel will be activated.
4
Set cooling/heating discharge temperature by clicking
[ ]and[ ].
When the Fresh duct is in Cool mode, the Fresh duct can
be set as cooling discharge
temperature and when the Fresh duct is in Heat mode,
the Fresh duct can be set as heating discharge
temperature.
When the Fresh duct is in Auto or Fan mode, the discharge
temperature cannot be adjusted.
Cooling discharge temperature can be set in the range of
15°C(59°F)~25°C(77°F).
Heating discharge temperature can be set in the range of
18°C(64°F)~30°C(86°F).
].