12
en | System setup - hardware
Circuit overloading
Consideration should be given to the connection of the equipment to the power supply
circuitry and the effect that any possible overloading of circuits might have on overcurrent
protection and power supply wiring. Appropriate consideration of equipment nameplate
ratings should be used when addressing this concern.
Reliable ground
A reliable ground must be maintained at all times. To ensure this, the rack itself should be
grounded. Particular attention should be given to power supply connections other than the
direct connections to the branch circuit (i.e. the use of power strips, etc.).
3.4

Rack mounting instructions

This section provides information on installing the chassis into a rack unit. There are a variety
of rack units on the market, which may mean the assembly procedure will differ slightly. You
should also refer to the installation instructions that came with the rack unit you are using.
Notice!
This rail will fit a rack between 26" and 33.5" deep.
3.4.1

Separating the sections of the rack rails

The chassis package includes two rail assemblies in the rack mounting kit. Each assembly
consists of two sections:
To separate the inner and outer rails:
1.
2.
2014.01 | V4 | DOC
an inner fixed chassis rail that secures directly to the chassis
an outer fixed rack rail that secures directly to the rack itself.
Locate the rail assembly in the chassis packaging.
Extend the rail assembly by pulling it outward.
Quick Installation Guide
DIVAR IP 6000 2U
Bosch Sicherheitssysteme GmbH