46
Loading a configuration into an RCU
The process for configuring an RCU can
occur on-site or be conducted in the
workshop. The sequence for loading a
configuration into the RCU is as follows:
1. Connect a USB antenna into a PC and
start RCU Connect.
2. Open the door of the RCU and power up
the RCU.
3. The user can load a configuration to a
RCU by clicking the "Configure RCU"
button from the main menu of RCU
Connect. If the user has no template
files or no layout files, RCU Connect will
prompt the user to import the files (see
Importing layout files and configuration
templates into RCU Connect section on
page 43). If RCU Connect cannot find
any layout files, or the user has more
than one layout file, RCU Connect will
open a file selection box allowing the
user to locate and select the desired
layout file. A layout file must be
selected, or the user will be returned to
the main menu. If RCU Connect cannot
find any configuration templates, or the
user has more than one configuration
template, RCU Connect will open a file
selection box allowing the user to locate
and select the desired configuration
template. A configuration template must
be selected, or the user will be returned
to the main menu.
4. When suitable layout files and
configuration templates have been
selected, the "Connection" screen is
displayed as shown in Figure 42.
It is recommended that only one RCU within the
workshop be powered up while configuration
occurs to simplify the process.