Huawei FusionModule1000A40 Product Description page 30

Prefabricated all-in-one data cente
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Product Description (Advanced Configuration, 208
V)
Item
Power distribution switches for smart
cooling product boxes
Power distribution switches for IT
equipment
An integrated UPS works when the input power is 208 V AC, and features
redundancy, high reliability, high efficiency, environment friendliness, high
flexibility, and intelligent and simple operations.
Table 3-5 Technical specifications of the integrated UPS
Category
Item
Mains input
Input system
parameter
Rated input voltage
Input voltage range
Input frequency range
Input power factor
THDi
Bypass input
Input system
parameter
Rated input voltage
Input frequency range
Output
Output system
parameter
Voltage
Frequency
Power factor
Transfer time
Output voltage
imbalance
Issue 03 (2021-02-10)
Specifications
Three-phase, four-wire, and PE
208 V AC (line voltage)
187–253 V AC (line voltage)
40–70 Hz
0.99 (full load); 0.98 (half load)
● THDi ≤ 3% (full linear load)
● THDi ≤ 5% (full non-linear load)
Three-phase, four-wire, and PE
208 V AC/220 V AC/230 V AC (line voltage)
50/60 Hz ±6 Hz (adjustable with the tolerance of
0.5–6 Hz, ±2 Hz by default)
Three-phase, four-wire, and PE
208 V AC/220 V AC/230 V AC±1% (line voltage)
In normal mode, the frequency is synchronous
with the bypass input frequency.
In battery mode, the frequency is 50/60 Hz
(tolerance ±0.25%).
1
● Uninterruptible transfer: 0 ms
● Interruptible transfer: ≤ 20 ms
Voltage imbalance: ±3%; phase imbalance: ±2°
Copyright © Huawei Technologies Co., Ltd.
Specifications
63 A/3P x 2
40 A/3P x 4
10 A/2P x 3
● 40 A/2P x 11 x 2
● 40 A/1P x 2 x 2