Siemens NXAIR M Operating Instructions Manual page 216

Air-insulated switchgear
Table of Contents

Advertisement

Panels with motor operating mechanism control
To block any access to the withdrawable circuit-breaker, turn the double-bit key until the
operating mode indicator changes to "T":
Fig. 366: Turning the key 90°
Remove the double-bit key and push the operating slide downwards as far as it will go.
Close the control door.
Fit a padlock to the control door and close the padlock.
Racking the withdrawable circuit-breaker is blocked.
216
To change from "H" to "T" turn 90° counter-clockwise
To change from "M" to "T" turn 180° counter-clockwise
counter-clockwise
HINT
Final procedure steps
You may now open the high-voltage door and take the withdrawable
circuit-breaker out of the panel.
HINT
When the control door is closed, the access mode indicator for the withdrawable
circuit-breaker is covered.
If required, open the control door to read the indicator.
from
to
Fig. 367: Turning the key 180°
NXAIR M
from
to
counter-clockwise
139-2021.9 / 07

Advertisement

Table of Contents
loading

This manual is also suitable for:

139-2021.9