Bosch HPC 410 Installation Instructions For Contractors

Bosch HPC 410 Installation Instructions For Contractors

User interface

Advertisement

Installation instructions for contractors
User interface
HPC 410
0010031776-002

Advertisement

Table of Contents
loading

Summary of Contents for Bosch HPC 410

  • Page 1 Installation instructions for contractors User interface HPC 410 0010031776-002...
  • Page 2: Table Of Contents

    Technical data........17 HPC 410 – 6721832682 (2021/02)
  • Page 3: Explanation Of Symbols And Safety Instructions

    ▶ Observe national and regional regulations, technical rules and guidelines. H Determined use ▶ Use the product only to control heating systems. Any other use is considered inappropriate. We take no responsibility for damage caused through incorrect use. HPC 410 – 6721832682 (2021/02)
  • Page 4: Product Information

    4. Once the user interface HPC 410 is connected to the power supply, Depending on the software version of the control unit, the texts shown in the Language menu appears on the display.
  • Page 5 [No] and confirm. [Back]: if changes are needed. Mixer heating [Yes] | [No]: setting that defines whether heating Table 1 Commissioning with the configuration wizard circuit 1 circuit 1 is a heating circuit with mixer. HPC 410 – 6721832682 (2021/02)
  • Page 6: Additional Settings At Commissioning

    ▶ To permanently shutdown: Disconnect power from the entire system [No]: Normal operation. Heating and DHW produced by and all BUS nodes. the heat pump and the additional heater/indoor unit. HPC 410 – 6721832682 (2021/02)
  • Page 7: Menu: Pumps

    Temp.diff. TC3/ 2...3...10 K: Set the permissible temperature differential TC0 Cool. between the heat pump flow and return in cooling mode. Table 3 Settings in the heat pump data menu HPC 410 – 6721832682 (2021/02)
  • Page 8: Menu: Smart Grid

    [-20...20] °C: The electric additional heater is allowed to start below the set outdoor temperature. 1) Not available if Germany is set as country. 2) Only available if Germany is set as country. Table 8 Settings in the electric additional heater data menu HPC 410 – 6721832682 (2021/02)
  • Page 9: Menu: Auxiliary Heater With Mixer

    Building type Measure of the thermal storage capacity of the heated building. 1) To get a more responsive regulation it is recommended to choose “No”. Table 10 Settings in the system data menu HPC 410 – 6721832682 (2021/02)
  • Page 10: Menu Priority Heating Circuit 1

    Remote ctrl [HPC 410]: HPC 410 controls the selected heating circuit Heating switch-off [1...1...48] h: Set the heating mode switch-off delay. The without remote control. delay timer activates when the outdoor temperature raises over [CR10]: CR10 is installed as remote control for the the threshold temperature.
  • Page 11 Room temperature – 10 ... 0 ... 10 K: parallel displacement of the heating offset curve (e.g. when the room temperature measured with a thermometer deviates from the set value) HPC 410 – 6721832682 (2021/02)
  • Page 12: Screed Drying Menu

    (starting point of the heating curve) and the interruption duration. end point. Underfloor heating Radiator system Minimum outside temperature – 10 °C – 10 °C 1,min Base point 25 °C 25 °C HPC 410 – 6721832682 (2021/02)
  • Page 13 [1 ... 3 ... 30] days: setting for the time delay between the beginning of the start phase and the next phase ( Fig. 6, [1]). Start phase temp. [20 ... 25 ... 55] °C: flow temperature during the start phase ( Fig. 6, [1]) HPC 410 – 6721832682 (2021/02)
  • Page 14: Dhw Settings

    Table 17 Settings in the DHW menu installed and to be controlled by the heat source, the DHW circulation pump must be activated here as well. [Off]: the DHW circulation pump cannot be controlled by the heat source. HPC 410 – 6721832682 (2021/02)
  • Page 15: Menu: Pool Settings

    Graphic configuration of the solar thermal system. [No]: No daily heat-up. configuration Daily heat-up time [00:00 ... 02:00 ... 23:45]: time for the start of the daily Current solar Graphic representation of the configured solar thermal heat-up. configuration system. HPC 410 – 6721832682 (2021/02)
  • Page 16: Settings For The Hybrid System

    The fault history can be deleted in the Reset menu ( Chapter, 4.9.7). Table 21 Information in the fault display menu HPC 410 – 6721832682 (2021/02)
  • Page 17: Table Of Contents 6 Environmental Protection And Disposal

    You can contact our Data Protection Officer under: Table 24 Technical data Data Protection Officer, Information Security and Privacy (C/ISP), Robert Bosch GmbH, Postfach 30 02 20, 70442 Stuttgart, GERMANY. You have the right to object, on grounds relating to your particular Environmental protection and disposal...
  • Page 18 Check the voltage at the terminals If the sensor values matched, but Table 28 of the flow temperature sensor at the voltage values do not, replace the heating circuit module the heating circuit module according to table HPC 410 – 6721832682 (2021/02)
  • Page 19 Test procedure/Cause Action Too low temperature of heating Open more thermostats on the system. heating system. Defective sensor TL2. Check sensor TL2 against sensor tables. Replace sensor TL2 If there is a deviation. Table 38 HPC 410 – 6721832682 (2021/02)
  • Page 20: Overview Of The Service Menu

    – ESC blocking time1 on – Internal heating pump – ESC blocking time2 on – Min. outside temp. – ESC blocking time3 on – Damping – Block additional heater – Building type – PV system HPC 410 – 6721832682 (2021/02)
  • Page 21 – Switch-on temp. EM – Change solar configuration – Switch-off temperature EM – Current solar configuration – DHW comfort – Solar parameters – Switch-on temperature –  Installer manual for the solar thermal system. – Switch-off temperature HPC 410 – 6721832682 (2021/02)
  • Page 22 – Solar – ... – Output limiter – ... – Fault displays – ... – System information – ... – Maintenance – ... – Reset – ... – Calibration – ... – SnapShot – ... HPC 410 – 6721832682 (2021/02)
  • Page 24 CONTROLS AND CONNECTIVITY TEAM: 0330 123 3641 APPOINTMENTS: 0330 123 9339 SPARES: 0330 123 9779 LITERATURE: 0330 123 9119 TRAINING: 0330 123 0166 SALES: 0330 123 9669 Bosch Thermotechnology Ltd. Cotswold Way, Warndon Worcester WR4 9SW United Kingdom Tel. 0330 123 9559 worcester-bosch.co.uk...