Outdoor Fan Control - Panasonic U-8ME1E8E Service Manual

2way system
Table of Contents

Advertisement

5. Outdoor Fan Controls
5-6. Silent Mode
This unit includes 2 types of silent modes.
Max. fan mode in silent mode
Outdoor unit cacacity -3dB mode -5dB mode
8 HP
10 HP
12 HP
14 HP
16 HP
18 HP
20 HP
Selecting the silent mode results in operation that gives priority to reducing noise, because these modes involve
restrictions on outdoor unit fan modes, the capacity will be somewhat reduced.
* The compressor capacity (frequency) is not limited. However, the capacity of the compressor decreases by road
map control because of the pressure caused by the decreased fan rotational speed.
* To activate this function, it is necessary to set it to each outdoor unit.
CODE: 05
Setting No
Silent mode
0
Invalidity
(Factory preset mode)
1
Silent is given priority
2
3
4
5
Capacity is given priority
6
7
8
9
Controlled in moderation
10
11
12
* When the setting is "external input to PCB necessary", this function works by short circuiting "SILENT" pins.
* When the setting is "external input to PCB unnecessary", this function always works.
* When the setting is "Capacity is given priority", this function works excluding the following conditions.
Condition that silent mode interrupts
Cooling operation: Ambient temperature ≧ 38℃
Heating operation: Ambient temperature ≦ 2℃
This function will be useful for nighttime in summer.
* When the setting is "Controlled in moderation", max. fan mode is decided in the following formula.
Max. fan mode = 14 - ( 35 – Ambient temperature) / 2
However, minimum fan mode is "6", maximum is "14". (When high static pressure mode, max is "15")
5-7. High Static Pressure Mode
The outdoor unit allows a high static pressure changing the settings.
The maximum permissible static pressure is 8 mmAq.
EEPROM setting in each outdoor unit
CODE: 8F
Setting No
0
Invalid
(Factory preset mode)
1
High static pressure mode
2 - 6
No use (Never use)
11
8
11
10
10
9
9
8
9
8
11
10
11
10
External input to PCB
-
Necessary
Unnecessary
Necessary
Unnecessary
Necessary
Unnecessary
1 - 17
Control Functions-Outdoor Unit
Max. effect
Capacity reduction
-
-
-3dB
Approx -1 HP
-5dB
Approx -2 HP
-3dB
Approx -1 HP
-5dB
Approx -2 HP
-3dB
Max. -1 HP
-5dB
Max. -2 HP
-3dB
Max. -1 HP
-5dB
Max. -2 HP
-3dB
Max. -1 HP
-5dB
Max. -2 HP
-3dB
Max. -1 HP
-5dB
Max. -2 HP
2WAY SYSTEM