17. Slim Low Static Ducted Type (M1 Type)
17. Slim Low Static Ducted Type (M1 Type)
17-5. Increasing the Fan Speed
For Short Circuit Connection
The standard (before shipment) external static pressure is shown in the table below.
When using with a higher static pressure, it is necessary to change to the high static pressure mode.
External static pressure
Type
Standard
High static pressure
When using with high static pressure mode, set the indoor unit control
board as shown at right.
Follow the below procedure while the unit is turned off.
(1) Open the cover of the electrical box and confirm that it is the indoor
unit control board.
(2) Connect the short circuit connector to the short circuit pin TP3 (2P:
Yellow) of the indoor unit control board.
In case of wired remote control setting, do not use the short circuit connector.
1
For Wired Remote Control
Press and hold the
4 seconds or longer.
"
," unit No. "
item code "
2
on the remote controller LCD display.
At this time, the indoor unit fan (or all indoor unit fans in the
case of group control) begins operating.
Press the temperature setting
buttons to select the item code
3
Press the timer time
setting data.
* For item codes and setting data, refer to the right table.
Press the
(The display stops blinking and remains lit,
and setting is completed.)
4
Press the
remote controller display.
S-15MM1E5
S-22MM1E5
40
5
30
L
20
10
6
0
4 5 6 7 8 9 10 11
Airflow (m
S-36MM1E5
7
50
40
30
20
8
10
0
4 5 6 7 8 9 10 11
Airflow (m
9
15
22
28
10
10
15
30
30
30
and
buttons simultaneously for
,
" (or "
" in the case of group control),
," and settings data "
/
"
".
/
buttons to select the desired
button.
button to return to normal
5
40
HH
30
H
20
10
L
H
HH
0
0
3
/minute)
60
50
5
HH
40
H
30
L
20
H
HH
10
L
0
0
12
3
/minute)
36
45
56
15
15
15
40
40
40
" are displayed blinking
External static pressure's
upper limit in high static
pressure mode
Standard external
5
S-28MM1E5
static pressure's
upper limit
HH
H
L
H
L
HH
0
Lower limit airflow
4 5 6 7 8 9 10 11
12
3
Airflow (m
/minute)
S-45MM1E5
5
HH
H
L
HH
HT
H
L
0
5 6 7 8 9 10 11 12 13
3
Airflow (m
/minute)
4-308
2WAY SYSTEM Unit Specifi cations
2WAY SYSTEM Unit Specifi cations
Indoor control board
2
6
1
5 1
Item
code No.
0000
Standard (setting at shipment)
0003 High static-pressure
HH
H
L
HH
H
L
3
Airflow (m
/minute)
S-56MM1E5
60
HH
50
5
H
40
L
30
HH
20
H
L
10
0
0
7 8 9 10 11 12 13 14 15
3
Airflow (m
/minute)
White Yellow Red
TP6 TP3 TP1
3
4
Description
Rated external static
pressure in high static
pressure mode
Lower static pressure
in high static pressure
mode
Rated external static
pressure at shipment
Upper limit airflow