Mitsubishi Electric MELSEC Q Series Handbook page 123

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
REPLACEMENT OF I/O MODULE
(6) Specifications comparison between A1SY22 and QY22
Specifications
Number of output points
Isolation method
Rated load voltage
Maximum load voltage
Maximum load current
Minimum load voltage/
current
Maximum inrush current
Leakage current at off
Maximum voltage drop at
on
Off  on
Response
time
On  off
Surge suppressor
Common terminal
arrangement
Operation indication
Fuse rating
(breaking capacity)
Fuse blown indication
External
Voltage
power
Current
supply
External connection
system
Applicable wire size
Applicable solderless
terminal
Current consumption
External dimensions
Weight
*1
Due to the characteristics of the triac, some precautions require re-checking before replacement.
For details, refer to Section 3.3 (4) to check if there are any precautions that fall under this category.
*2
Connect a fuse to every external terminal to prevent the external device and module at load short from burnout.
Also, configure an external circuit if fuse blown indication is required.
A1SY22
16 points
Photocoupler
100/240VAC 50/60Hz ±3Hz
264VAC
0.6A/point, 2.4A/common
24VAC 100mA
100VAC 10mA
240VAC 20mA
20A 10ms or less
8A 100ms or less
1.5mA (120VAC 60Hz)
3mA (240VAC 60Hz)
1.5VAC or less (0.1 to 0.6A)
1.8VAC or less (50 to 100mA)
2VAC or less (10 to 50mA)
1ms or less
1ms + 0.5 cycles or less
CR absorber
(0.01µF + 47)
8 points/common
(common terminal: TB9, TB18)
On indication (LED)
5A
(1 fuse/common)
Cannot be changed.
Available
(LED turns on when a fuse is blown
and a signal is output to the CPU
module.)
100-240VAC (85 to 264VAC)
2mA (typ. 200VAC/common)
20-point terminal block connector
(M3.57 screws)
2
0.75 to 1.25mm
R1.25-3.5, R2-3.5,
RAV1.25-3.5, RAV2-3.5
0.27A (typ. all points on)
130(H)34.5(W)93.6(D)mm
0.24kg
*1
: Compatible,
QY22
16 points
Photocoupler
100 to 240VAC 50/60Hz ±5%
264VAC
0.6A/point, 4.8A/common
24VAC 100mA
100VAC 25mA
240VAC 25mA
20A 1 cycle or less
1.5mA or less (120V 60Hz)
3mA or less (240V 60Hz)
1.5V or less
1ms + 0.5 cycles or less
1ms + 0.5 cycles or less
(rated load, resistance load)
CR absorber
16 points/common
(common terminal: TB17)
On indication (LED)
None
(Connecting a fuse to external wiring
is recommended.)
-
-
18-point terminal block
(M36 screws)
2
Core: 0.3 to 0.75mm
(outside diameter: 2.8mm or less)
R1.25-3
(Sleeved solderless terminal cannot
be used.)
0.25A (MAX. all points on)
98(H)27.4(W)112.3(D)mm
0.40kg
: Partially changed, : Incompatible
Compat-
Precautions for replacement
ibility
Carefully select a load for use
since the minimum load current
is increased.
As the common is changed from
2 commons to 1 common, wiring
with a different voltage for each
common is not possible.
*2
Fuses are not built in.
An external power supply is not
required.
Wiring change is required.
Wiring space is narrower.
The weight is increased.
3
- 70