Panasonic PAW-160MAH2L Installation Instructions Manual page 73

Air handling unit kit
Table of Contents

Advertisement

Allocation
Terminal No.
X6
M2.1
X6.1
4 - 20 mA
l
M2.2
X6.2
Potential of M2.1
l
l
M2.3
X6.3
0 to 10 V DC
M2.4
X6.4
Potential of M2.3
l
M2.5
X6.5
No polarity
l
l
M2.6
X6.6
No polarity
COM
X6.7
Potential for DI1 to DI3
l
DI1
X6.8
Digital Input 1
l
l
DI2
X6.9
Digital Input 2
DI3
X6.10
Digital Input 3
l
COM
X6.11
Potential for DO2
l
l
DO2
X6.12
Alarm Signal
COM
X6.13
Potential for DO1
l
DO1
X6.14
Operation Signal
l
Terminal layout – CZ-CAPBC2 / ACC-SP1A
For information on the terminal layout of CZ-CAPBC2 / ACC-SP1A see →
out – CZ-CAPBC2 / ACC-SP1A, p.
AHU Kit – Installation Instructions – 09/2021
Function
Analogue output terminals
Analogue input terminals for temperature and demand
control
Activation of demand control
Digital Inputs
(For information on functionality refer to section
"Terminal layout – CZ-CAPBC2 / ACC-SP1A" in this
document)
Alarm Signal
Operation Signal
69.
Electrical Wiring
Description
Analog output (Room temperature monitor), Indoor temperature
monitor output. Output current : 4 to 20 mA. Temperature indica-
tion range : 5 to 36 °C, 0.5 °C step
Analogue input (+10 V DC) for demand control / temperature
control
Analog input Negative potential (–10 V DC) for demand control /
temperature setting
Insert bridge to activate temperature control (system is set for
demand control as standard)
2 types of usage:
a) Potential-free:
Keep S3 of CZ-CAPBC 2/
ACC-SP1A on "NON VOLTAGE".
b) 12 to 24 V DC, 10 mA external: Change S3 of CZ-CAPBC2 /
ACC-SP1A to "VOLTAGE".
External Potential: max. 230 V AC / 3 A
External Potential: max. 230 V AC / 3 A
5.3 Terminal board lay-
5
73