Panasonic PAW-160MAH2L Installation Instructions Manual page 72

Air handling unit kit
Table of Contents

Advertisement

Electrical Wiring
Terminal No.
X4
TA1
X4.1
l
TA2
X4.2
l
l
E1.1
X4.3
E1.2
X4.4
l
E2.1
X4.5
l
l
E2.2
X4.6
OP1
X4.7
l
OP2
X4.8
l
l
OP3
X4.9
OP4
X4.10
l
OP5
X4.11
l
l
OP6
X4.12
OT1
X4.13
l
OT2
X4.14
l
5
l
OT3
X4.15
OT4
X4.16
l
OT5
X4.17
l
l
OT6
X4.18
Terminal No.
X5
U1
X5.1
l
l
U2
X5.2
R1
X5.3
l
R2
X5.4
l
l
R1
X5.5
R2
X5.6
l
To be continued on next page.
72
Allocation
Function
No polarity
Suction Temperature Sensor TA (included)
(Room Temperature Sensor)
No polarity
No polarity
Sensor E1 / TH2
No polarity
No polarity
Sensor E2 / TH3
No polarity
12 V DC
12 V DC
Potential of Defrost
Defrost signal output
Potential for Thermostat
Thermostat signal output
Potential for Cool start
Cool operation signal output
Potential for Heat start
Heat operation signal output
Potential for Fan start
Fan (free cooling) operation signal output
Potential for OT2 - OT6
COM
Heat input
Heat mode input
Cool input
Cool mode input
Demand Input 1
LV1 demand control input
Demand Input 2
LV2 demand control / QUIET input
LV3 demand control / EXCT (forcibly thermostat off)
Demand Input 3
input
Allocation
Function
No polarity
Communication bus wiring P-link
No polarity
No polarity
Terminal for Group Wiring (RC connection)
No polarity
No polarity
Terminal for Group Wiring (RC connection)
No polarity
Description
12 V DC relay required for each signal output, field supplied
5 V DC 0.5mA Current input
Demand control, QUIET and EXCT inputs must be
set using indoor unit detailed settings, parameter code
0002EE, please see relevant technical data service manual for
details. 5 V DC 0.5mA Current input
Description
Required for centralized controller
Internal Potential: 16 V DC
Internal Potential: 16 V DC
AHU Kit – Installation Instructions – 09/2021