ABB ACS560 Quick Installation And Start-Up Manual page 20

Standard control program
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

20 EN - Quick installation and start-up guide
7. Prepare the ends of the input power cable and motor cable as illustrated in the figure. If
you use aluminum cables, put grease on the peeled aluminum cable before connecting it
to the drive. Two different motor cable types are shown in the figures (7a, 7b).
Note: The bare shield is grounded 360°. Mark the pigtail made from the shield as a PE
conductor with yellow-and-green color.
6
EN
HI
8. Slide the cables through the holes of the lead-through plate and attach the grommets to
the holes (the motor cable to the right and the input power cable to the left).
9. Connect the motor cable as follows:
Ground the shield 360° under the grounding clamps.
Connect the twisted shield of the cable to the grounding terminal (9a).
Connect the phase conductors of the cable to terminals T1/U, T2/V and T3/W. Tighten
the screws to the torque given in the figure (9b).
Note: Frame R8 only:
If you connected the connector to only one conductor, ABB recommends to put the
conductor under the upper pressure plate.
The connectors are detachable, but ABB recommends not to detach them. If you do,
detach and reinstall the connectors as follows.
Input power cable
10. Connect the input power cable as in step 9.
7a
7b
7b
PE
7a
PE

Hide quick links:

Advertisement

Table of Contents
loading