122 Diagnostics
Code
Fault / Aux. code
(hex)
aux code visible
only on assistant
control panel and
drive composer))
8006
8007
EN
8008
HI
8009
800A
64A1
Internal file load
64A4
Rating ID fault
64A6
Adaptive program
64B1
Internal SSW fault
1 - Starting OS time tick failed
2 - Creating system tasks failed
3 - Initializing file system failed
4 - Checking file system failed
64B2
User set fault
64B3
Macro parameteriza-
tion error
64E1
Kernel overload
6581
Parameter system
6591
Backup/Restore
timeout
65A1
FBA A parameter
conflict
Cause
Not enough memory for the ap-
plication.
The application contains the
wrong system library version.
The application is empty.
The application contains invalid
tasks.
The application contains an un-
known target (system) library
function.
File read error.
Rating ID load error.
Fault in adaptive program.
A fatal error in the power-up
phase of System Software
(SSW).
5 - Initializing WoRm volumes failed
6 - Loading FPGA configuration failed
7 - Loading application program failed
Loading user parameter set
failed.
Macro parameterization failed,
eg. Parameter default value that
cannot be changed has been at-
tempted to write.
Operating system error.
Note: This fault cannot be reset.
Parameter load or save failed.
During backup creating or
restoring operation a panel or
PC-tool has failed to communic-
ate with the drive as part of this
operation.
Requested functionality is not
activated.
What to do
Reduce the size of the application. Reduce
the number of parameter mappings.
See the drive-specific log generated by
Automation Builder.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
In Automation Builder, give a "Clean" com-
mand and reload the application.
In Automation Builder, check application
task configuration, give a "Clean all" com-
mand, and reload the application.
Update the system library or reinstall Auto-
mation Builder.
See the drive-specific log generated by
Automation Builder.
Reboot the control unit. If the problem per-
sists, contact ABB.
Contact ABB.
Check the fault code extension.
SSW runs in partial functionality mode.
Make sure a valid user parameter set exists.
Reload if uncertain.
Reboot the control unit using parameter
96.08 Control board boot or by cycling
power. If the problem persists, contact ABB.
Try forcing a save using parameter 96.07
Parameter save manually.
Check panel or PC-tool communication and
if it is still in backup or restore state.
Check PLC programming.
Check parameter groups 50 Fieldbus ad-
apter (FBA) and 51 FBA A settings.