Air Filter Cleaning - GE Kelman Minitrans Operator's Manual

Transformer oil dissolved gas and moisture monitor
Hide thumbs Also See for Kelman Minitrans:
Table of Contents

Advertisement

8

AIR FILTER CLEANING

The product draws air from the left-hand side and expels it on the right. The intake air is
filtered to remove the largest particles, so depending on environmental conditions the
air filter as shown in Figure 8-1 and may need occasional cleaning. The outlet filter may
also require attention.
Note:
A higher temperature in zone two can be an indication that such action is
required.
Figure 8-1: Air filter assembly without cover
To clean the air filter:
1.
switch.
2.
To remove the cover, use a flat-head screwdriver or the supplied tab-pushing tool
to push the tab on the lower part of the fan cover as shown in Figure 8-1.
3.
If a cable-tie is fitted to the filter holder, first carefully remove it. Remove the filter
holder by pulling off the black snap-off cover to the filter as shown in Figure 8-2.
4.
If the filter mat is just dusty, clean it with dry compressed air or by beating it
against a hard clean surface.
5.
If the filter mat is oily, clean it with mild detergent and water, and then dry it
thoroughly.
6.
Replace the filter mat and snap the cover back in place. Note: The cable tie only
secures the filter holder during shipping so there is no requirement to replace.
7.
Repeat for the other filter.
8.
Re-energise the product and it will automatically begin measuring at the next
scheduled time.
MA-006- Minitrans Operator Guide - Rev 2.2
First isolate the product through the external circuit breaker or external
Figure 8-2: Air filter with cover
5-Mar-20
Page 21 of 26