7. Set the parameter p0290 "Power unit overload response" to 1 to prevent different responses
of the Motor Module Booksize connected in parallel in the event of an overload.
8. Set the parameter p3900 "Completion of quick commissioning" to 3 to complete the quick
commissioning with the calculation of the motor, open loop control and closed loop control
parameters.
9. Back up the created configuration by saving it on the memory card (ROM) as follows:
Click the icon
- OR -
Call the "Target device > Copy RAM to ROM" shortcut menu.
10.Make additional application-specific settings of the parameterization of the corresponding
drive parameters by using the expert list.
11.We recommend optimizing the drive parameters by identifying the drive during the system
commissioning.
To do this, perform a standstill measurement (p1910) and, if possible, a rotating
measurement (p1960).
Motor Modules Booksize parallel connection
Application Manual, 01/2020, 6SL3097-5BF00-0BP0
"Copy RAM to ROM"
5.5 Step 3: Parameterizing the drive object
Commissioning
41