PT2009-A1
PTO2006-A1
PT2008-A1
A6V11899865_en--_b
'Desk call station (RS485, 8+1)'
Call station with 8 configurable, illuminated zone buttons plus talk button
Buttons are freely operable
Electret condenser microphone with gooseneck
Monitored microphone
Symmetrical audio transmission, analog
'PACE-Bus' (RS485) data transmission
Audio output 0 dB (line volume)
Connection to control panel via CAT5 cable or above (max. 500 m) and RJ45
connector
Up to 5 call stations can be configured in a cascade 'daisy chain'
Adapter module PTO2008-A1 for connection to the control panel
Option to add up to three extension modules, each with 8 zone buttons
Addressable via 8-way SIP (Single Inline Package) switch in device
Insertable labels for custom button identification
Robust sheet steel housing
'Call station extension (RS485, 8)'
Optional button extension for desk call station PT2009-A1
Up to 3 button extensions possible for desk call station PT2009-A1, offering a
total of 32 buttons
8 configurable, illuminated zone buttons
Insertable labels for custom button identification
'Desk call station (analog, 3+1)'*
Call station with 3 configurable zone buttons plus talk button
Buttons are freely operable.
Electret condenser microphone with gooseneck
Symmetrical audio transmission, analog
Audio output 0 dB (line volume)
Control signals for zones 1-3 and 'Talk'
Connection to control panel via CAT5 cable or above (max. 150 m) and RJ45
connector
Supplied adapter module for connection to control panel
Insertable labels for custom button identification
Robust sheet steel housing
* The desk call station PT2008-A1' may only be used for standard applications
and not for alarm applications.
Operating elements in the system
Call stations
4