FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator)
Figure 5-35 Removing the access control device
Step 2 Remove cables from the old access control device and connect the cables to the
new one.
Step 3 Install the new access control device on the baseplate and secure the device using
screws at the bottom.
Step 4 Log in to the ECC800-Pro WebUI, choose System Settings > Access Management,
and perform the Synchronize Permission operation.
Step 5 Verify that the access control system is normal.
----End
5.4.3.3 Replacing a Button
Context
●
●
●
Impact on the System
The faulty button cannot be used.
Preparations
●
●
Issue 01 (2020-12-25)
The light button and door open button (green) can reset automatically. Both
BOM numbers are 16050101.
The emergency button (red) needs to be manually reset. Its BOM number is
16050102.
The door open button, emergency button, and light button are replaced in the
same way.
Tool: socket wrench
Material: door open button, emergency button, or light button