FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator)
Figure 5-62 Water sensor components
(1) Water detector
(4) Conversion cable end B,
connecting to water the
detection rope
Impact on the System
The water leakage of the data center cannot be sensed.
Preparations
●
●
Procedure
Step 1 Replace the water detector.
1.
2.
3.
4.
Issue 01 (2020-12-25)
Material: water sensor
Skill requirement: hardware installation engineers
Remove the conversion cable at the conversion port for the water detector
and conversion cable.
Remove the communication cable from the water detector.
Connect a new water detector to the conversion cable.
Secure the new water detector.
Copyright © Huawei Technologies Co., Ltd.
(2) Conversion cable end A,
connecting to the water detector
(5) Water detection rope end A,
connecting to the conversion cable
5 Parts Replacement
(3) Conversion cable
(6) Water detection rope
112