NOTICE
Damage due to overheating
An inclined installation reduces the convection by the HMI device and therefore the
maximum permitted ambient temperature for operation.
If there is sufficient convection from forced ventilation, the HMI device can also be operated
in the inclined mounting position up to the maximum permitted ambient temperature for
vertical installation. The HMI device may otherwise be damaged and its certifications and
warranty will be void.
Note
Extended inclination and ambient temperature range
You can operate the 7", 9" and 12" devices with extended inclination and extended
temperature range under the following conditions:
• The USB load does not exceed 100 mA per USB port.
• The +24 V DC connection of the PROFIBUS interface is not used.
The following mounting positions and temperature ranges are permitted under the specified
conditions:
• Vertical mounting in landscape format with a maximum ambient temperature of +55 °C
• Mounting in landscape format with an inclination of up to 40° from the vertical with a
For information regarding the permitted ambient temperatures, refer to section "Climatic
ambient conditions (Page 42)".
Mounting position
Select one of the approved mounting positions for your HMI device.
Mounting in horizontal format
All HMI devices are suitable for horizontal mounting positions.
A maximum ambient temperature of +50 °C is permitted for vertical mounting (0° tilt angle);
a maximum of +40 °C is permitted for inclined mounting.
Comfort Panels INOX PCT
Compact Operating Instructions, 07/2021, A5E38804191-AE
maximum ambient temperature of 40 °C
Installing and connecting the device
3.1 Preparing for installation